Dust Collector Controllers

For specifications, wiring diagrams, and general information refer to reference section. For the T2310 and T2320 timer boards, DNC-T2300-DSP, and DNC-T2300-I/O, refer to specification drawing or manual for programming instructions.

All AMETEK NCC dust collector boards are UL/CUL rated except where noted. 


Q. I forgot my password for the DNC-PS700-A10 pressure differential meter.

A. There is an emergency security password available, call in to NCC for this value. 


Q. Can several Dust Collector controls share same pressure switch contact

A. No must be isolated switch on each input.


Q. What is the main difference between your series of controllers that have A10 or B10 in the suffix?

A. A10 controllers have OFF times from 1.5 to 30 seconds. B10 controllers have OFF times from 8.5 to 180 seconds. Both models have standard adjustable ON times from .05 to .5 seconds. 


Q. What is the maximum recommended length to run pressure lines to controller?

A. 50 feet max 


Q. How many solenoids can I connect on one output?

A. You can hook up to three as long as you maintain under current rating of 200VA (150VA for DNC-T2610-010 and -020) 